run 21 game,english betting sites,india slot machines,TRANSDUCER MODEL 6332/6332D
Request Quote is-caesars-casino-online-legit slots-fortune:-free-slot-machines- Analog output makes it easy to integrate with other equipment
- Smart probe technology lets you change probes without recalibrating the transducer
- Purchase probes separately and choose the ones that meet your application needs
- Quality Control monitoring and controlling air velocity and distribution during drying/ shaping process
- Combined with thermographic system measure air velocity across the board to evaluate the cooling efficiency
- 6332D comes with a display 6332 does not have a display
- Airflow transducers are designed for fixed installation
- Use on your production line quality control system
- Monitor facility exhaust ventilation system.
- Transducers feature 0 to 5 VDC or 4 to 20 mA analog output so you can send your data to other instruments such as data loggers, alarms, or controllers.
- Selectable Output (Output can be set to either voltage (0 to 5V) or current (4 to 20mA))
General Specifications | |
Analog Output | Current output: DC 4~20mA (Max. load resistance: 250Ω) Voltage output: DC 0~5V |
Display Resolution (Model 6332D only) | 0.01m/s (Velocity Range: 0 to 2, 0 to 5, 0 to 10 m/s) 0.1m/s (Velocity Range: 0 to 25, 0 to 50 m/s) |
Response Time | Display: 0.3 second Sampling: 0.1 second Output: 0.1 second |
Power Supply | DC 12 to 24V |
Operating Temperature Range | 41 to 104 ºF (5 to 40 ºC) with no condensation |
Storage Temperature Range | 14 to 122°F (-10 to 50°C) with no condensation |
Dimensions | 128(W)×78(D)×30(H) mm |
Weight | 0.7 lbs (320g) |
Warranty | 1 year |
What’s Included | Meter, Operation Manual |
Airflow Transducer Probes (See Table Below) | |
Measurement Specifications | |
Air Velocity | |
Ranges | 0.1 to 25.0 m/s 0.1 to 50.0 m/s |
Accuracy | +/- (3% of READING +/- 0.1) m/s |
Operating Temperature Range | -4 to 158°F (-20 to 70°C) with no condensation |
Storage Temperature Range | 14 to 122°F (-10 to 50°C) with no condensation |
Warranty | 1 year |
What’s Included | Probe, Data ROM, NIST TRACEABLE CALIBRATION Certificate |
0962-00 | 0963-00 | 0965-00 | 0965-01 | 0965-03 | 0965-04 | 0965-07 | 0965-08 | 0965-09 | 0965-10 | |
Air Velocity Range (m/s) | 0.1 to 50.0 | 0.1 to 50.0 | 0.1 to 25.0 | 0.1 to 25.0 | 0.1 to 25.0 | 0.1 to 25.0 | 0.1 to 25.0 | 0.1 to 25.0 | 0.1 to 50.0 | 0.1 to 50.0 |
Airflow Directivity | Mono | Mono | Omni | Omni | Omni | Omni | Omni | Omni | Omni | Omni |
Probe Type | Rod | Rod | Spherical | Spherical | Miniature | Miniature | Miniature | Miniature | Spherical | Spherical |
Air Velocity | O | O | O | O | O | O | O | O | O | O |
Acclimation time (sec) | 1 | 1 | 7 | 7 | 7 | 7 | 7 | 7 | 7 | 7 |